Megger Test Record

ElectricalTestingMotor

Executive Overview

The Megger Test Record is the structured recording format behind the single most important engineering discipline in flood and moisture-related motor recovery: judging insulation condition by trend, not by one reading. This page is the record itself — usable directly from the browser or printed — plus the reasoning for why each column exists.

Purpose

A single insulation resistance (IR) reading, taken once, tells you almost nothing about whether a motor is recovering or not. This record exists to capture a sequence of readings — baseline through post-drying — so that the trend itself becomes the evidence, following the same discipline built into the flagship Handbook article and referenced by IEEE 43.

When to Use

Classification

Engineering Discipline
Electrical
Machine Types
Motor, Generator, Transformer
Industries
All — general-purpose

Required Inputs

Expected Outputs

A completed trend table (below) showing IR and calculated Polarization Index (PI = 10-minute reading ÷ 1-minute reading) across each drying/testing stage — the primary input to a recovery-level determination in the Recovery Assessment Worksheet.

The Record

Megger Test Record — IR / PI Trend Log
Date/TimeIR @ 1 minIR @ 10 minPI (10min÷1min)Ambient TempNotes
Baseline (as-found)Before any drying
Day 1
Day 2
Day 3Compare trend against Acceptance Criteria below
Day 4 (if needed)

Procedure

  1. Confirm electrical isolation and lockout before connecting any test equipment.
  2. Record the baseline reading immediately — even a very low as-found value is useful data, not a result to discard.
  3. Dry the machine per the applicable method for the exposure type.
  4. Re-test at consistent intervals (e.g., daily), recording ambient temperature each time.
  5. Calculate PI at each stage: 10-minute reading ÷ 1-minute reading.
  6. Plot or visually compare the trend across all rows before drawing any conclusion.

Acceptance Criteria

AnalysisA stable or rising IR/PI trend across at least 3 consecutive readings supports proceeding with repair-level recovery. A flat or declining trend — even if one individual reading is numerically "acceptable" — is evidence against it and should trigger further evaluation before re-energizing.

The specific pass/fail numeric threshold is always the machine's own OEM documentation or the applicable standard's guidance — never a generic universal number. This record captures the trend; interpretation still requires engineering judgement.

Engineering Notes

Note
Record ambient temperature every time — insulation resistance is temperature-sensitive, and an uncorrected comparison across different temperatures can make a genuinely improving trend look flat, or vice versa.

Typical Mistakes

Common Mistake
Filling in only the baseline and one "final" reading, skipping the intermediate days — this defeats the entire purpose of the record, since the trend (not the endpoints alone) is the evidence.
Common Mistake
Using a test voltage that doesn't match the machine's rated voltage class. Always confirm against the nameplate first.

Related Content

Related Standards
IEEE 43 →IEC 60034 →
Related Knowledge Package
Flood-Damaged Electric Motor →
Related Engineering Evidence
Not yet available — Evidence Library has no published pages yet.

Future Download Formats

📄 PDF (planned)📊 Excel (planned)

The web version above is fully usable today — print this page directly, or fill it in on-screen. Downloadable formats follow in a future release.

Revision History